UPS battery
< Back to the UPS Battery main page | Upgrade to MAXRATE™ -12-400 Premium Plus

 High Rate UPS battery

UPS12-370
Valve Regulated Lead Acid Battery
for UPS standby power applications
12V 100 AH @ 20 hr rate,
12V 391 watts/cell @ 15 min. rate

FEATURES

  • Flame-arresting one-way pressure-relief vent for safety and long life.
  • Thermally welded case-to-cover bond to eliminate leakage.
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.
  • Computer-generated grid design optimized for high power density.
  • UL-recognized component.
  • Multicell design for economy of installation and maintenance.
  • Can be mounted in any orientation.
  • Not restricted for air transport – Complies with IATA/ICAO Special Provision A67.
  • Not restricted for surface transport – Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.
  • Computer designed lead, low calcium alloy grid for minimal gassing and ease of recycling.
  • Case and cover available in both standard and flame retardant polypropylene.
  • Flame retardant polypropylene case and cover compliant with UL 1778 (optional).


*All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C&D Representative for complete dimensional information.

UPS12-370 - Specifications
Cells Per Unit
Voltage
Per Unit
Weight
Electrolyte
Max. Discharge Current
Short Circuit Current
Ohms Imped.
60 Hz
6
12.84
74 lbs.
34 kg.
Absorbed H2SO4
SG = 1.300
800 Amps
5100 Amps
@ 0.1 sec.
0.0025 Ohms
Capacity

 

391 watts per cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C).

100 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C).
85 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F).
Operating Temperature Range  Discharge; -40°F (-40°C) to +160°F (71°C).

Charge; -10°F (-23°C) to + 140°F (60°C). (with temperature compensation)

Nominal Operating Temperature Range
+74°F (23°C) to +80°F (27°C).
Float Charging Voltage
 
13.5 to 13.8 VDC/unit Average at 77°F (25°C).
Recommended Maximum Charging Current Limit
 
C/5 amperes (20 amperes @ 100% depth of discharge) @ 20 hour rate.
Equalization and Cycle Service Charging Voltage 14.4 to 14.8 VDC/unit Average at 77°F (25°C).
Maximum AC Ripple (Charger)  

0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.

Maximum voltage allowed = 1.4% RMS (4% P-P).
Maximum current allowed = 5 amperes RMS (C/20).

Self Discharge

Dynasty UPS batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required. For higher temperatures the time interval will be shorter.
Accessories
 
Inter unit connectors, racks and cabinet systems are available.
Terminal
 
"L" terminal with 0.28" clearance hole to accept 0.25" (6mm) bolt.
Terminal Hardware Initial Torque
 
65 in.-lbs. (7.4 N-m).
Terminal Hardware Annual Retorque  52 in.-lbs. (5.88 N-m).

Note: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

 