Installation and maintenance programs
are available with custom cabling, racking or cabinets along with chargers,
inverters and power boards.
Electro
Battery is the complete source
for all your battery needs!
230 West Parkway US · Pompton Plains,
NJ 07444
Phone: 973-835-3334. Fax: 973-835-2332
email address: info@electrobattery.com
|

<
Back to the UPS Battery main page | Upgrade
to MAXRATE
-12-400 Premium
Plus
UPS12-370
Valve Regulated Lead Acid Battery
for UPS standby power applications
12V 100 AH @ 20 hr rate,
12V 391 watts/cell @ 15 min. rate
FEATURES
- Flame-arresting one-way pressure-relief vent for safety and
long life.
- Thermally welded
case-to-cover bond to eliminate leakage.
- Absorbent Glass Mat
(AGM) technology for efficient gas recombination of up to 99% and freedom
from electrolyte maintenance.
- Computer-generated grid design optimized for high power density.
- UL-recognized component.
- Multicell design
for economy of installation and maintenance.
- Can be mounted in
any orientation.
- Not restricted for
air transport – Complies with IATA/ICAO Special Provision A67.
- Not restricted for
surface transport – Classified as non-hazardous material as related
to DOT-CFR Title 49 parts 171-189.
- Computer designed
lead, low calcium alloy grid for minimal gassing and ease of recycling.
- Case and cover available
in both standard and flame retardant polypropylene.
- Flame retardant polypropylene
case and cover compliant with UL 1778 (optional).




|
*All dimensions in inches and (millimeters). All dimensions
are for reference only. Contact a C&D Representative for complete
dimensional information.
|
|
UPS12-370 - Specifications
|
|
Cells Per Unit
|
Voltage
Per Unit
|
Weight
|
Electrolyte
|
Max. Discharge Current
|
Short Circuit Current
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
74 lbs.
34 kg.
|
Absorbed H2SO4
SG = 1.300
|
800 Amps
|
5100 Amps
@ 0.1 sec.
|
0.0025 Ohms
|
Capacity
|
391 watts per
cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C).
|
| 100 Ah @ 20 hr. rate
to 1.75 volts per cell @ 77°F (25°C). |
| 85 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F). |
| Operating Temperature Range |
Discharge;
-40°F (-40°C) to +160°F (71°C). |
Charge; -10°F (-23°C) to + 140°F (60°C). (with temperature compensation)
|
Nominal Operating
Temperature Range
|
+74°F (23°C) to +80°F (27°C). |
Float Charging Voltage
|
13.5 to 13.8 VDC/unit Average at 77°F (25°C). |
Recommended Maximum
Charging Current Limit
|
C/5 amperes (20 amperes @ 100% depth of discharge) @
20 hour rate. |
| Equalization and Cycle Service Charging Voltage |
14.4 to 14.8 VDC/unit Average at 77°F (25°C). |
| Maximum AC Ripple
(Charger) |
0.5% RMS or 1.5%
P-P of float charge voltage recommended for best results.
|
| Maximum voltage allowed
= 1.4% RMS (4% P-P). |
| Maximum current allowed
= 5 amperes RMS (C/20). |
|
Self Discharge
|
Dynasty UPS batteries may be stored for up to 6 months
at 77°F (25°C) and then a freshening charge is required. For higher
temperatures the time interval will be shorter. |
Accessories
|
Inter unit connectors, racks and cabinet systems are
available. |
Terminal
|
"L" terminal with 0.28" clearance hole to accept 0.25"
(6mm) bolt. |
Terminal Hardware Initial Torque
|
65 in.-lbs. (7.4 N-m). |
| Terminal Hardware Annual Retorque |
52 in.-lbs. (5.88 N-m). |


| Note: |
Batteries to be
mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation.
Specifications subject to change without notification. |

<
Back to the UPS Battery main page
|





We also offer our customers, depending
on their needs, different kinds of battery junk removal programs utilizing
EPA approved disposal centers and/or smelters.
|