UPS12-100 - Specifications
|
|
Cells
Per Unit
|
Voltage
Per Unit
|
Weight
|
Electrolyte
|
Maximum Discharge Current
|
Short Circuit Current
|
Ohms Imped. 60 Hz 
|
| 6 |
12.84 |
21 lbs.
10 kg. |
Absorbed H2SO4
SG = 1.300 |
500 Amps |
1750 Amps
@ 0.1 sec. |
0.0060 Ohms |
| Capacity |
91.0 watts per cell at the 15 minute rate to 1.67 volts
per cell at 77°F (25°C). |
| 26.0 Ah @ 20 hr.
rate to 1.75 volts per cell @ 77°F (25°C). |
| 23.6 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°F (68°C).
|
| Operating Temperature Range |
Discharge; -40°F (-40°C) to +160°F (71°C). |
Charge; -10°F
(-23°C) to +140°F (60°C). (with temperature
compensation) |
| Nominal Operating
Temperature Range |
+74°F (23°C)
to +80°F (27°C). |
| Float Charging Voltage |
13.5 to 13.8 VDC/unit Average at 77°F (25°C). |
| Recommended Maximum Charging Current Limit |
C/5 amperes (5.2 amperes @ 100% depth of discharge) @
20 hour rate. |
| Equalization and Cycle Service Charging Voltage |
14.4 to 14.8 VDC/unit Average at 77°F (25°C). |
| Maximum AC Ripple
(Charger) |
0.5% RMS or 1.5% P-P of float charge voltage recommended
for best results. |
| Maximum voltage allowed = 1.4% RMS (4% P-P). |
| Maximum current allowed = 1.3 amperes RMS (C/20). |
| Self Discharge |
Dynasty UPS batteries may be stored for up to 6 months
at 77°F (25°C) and then a freshening charge is required. For higher
temperatures the time interval will be shorter. |
| Accessories |
Inter unit connectors, racks and cabinet systems are
available. |
| Terminal |
Flag terminal with 0.22" clearance hole to accept 0.1875"
bolt. |
| Terminal Hardware Initial Torque |
40 in.-lbs. (4.5 N-m). |
| Terminal Hardware Annual Retorque |
32 in.-lbs. (3.48 N-m). |