TEL12-105F
TEL12-105FS
Valve Regulated Lead Acid Battery
for communications standby power applications
FEATURES
- Flame-arresting one-way pressure-relief vent for safety and
long life.
- Thermally welded
case-to-cover bond to ensure a leak-proof seal.
- Flame-retardant polypropylene case and cover compliant with
UL94 V-0 with an Oxygen Limiting Index of greater than 28.
- Absorbent Glass Mat
(AGM) technology for efficient gas recombination 99% plus.
- Thick positive plate
design for maximum service float life – 10 year design life.
- Front accessible
threaded copper alloy terminals for ease of assembly and reduced maintenance.
- Complies with UL1778,
924, 1989 and 94 V-0.
- UL-recognized component.
- Can be used in any
orientation. Upright, side or end mounting recommended.
- Multicell design
for ease of installation and maintenance.
- Not restricted for
air transport – Complies with IATA/ICAO Special Provision A67
- Not restricted for
surface transport – classified as non-hazardous material as related
to DOT-CFR Title 49 parts 171-189
- Not restricted for
water transport – classified as non-hazardous material per IMDG Amendment
27.
- Battery design allows
for 48VDC configuration in a standard 23" relay rack in less than 10"
height.
- Minimizes battery
interconnection cost and resistance with supplied copper connectors.
- TEL12-105F overall
length = 22.51"
- TEL12-105FS overall
length = 21.95"




|
*All dimensions in inches and (millimeters). All dimensions
are for reference only. Contact a C&D Representative for complete
dimensional information.
|
|
TEL12-105F/FS - Specifications
|
|
Cells
Per Unit
|
Voltage
Per
Unit
|
Weight
|
Electrolyte
|
Maximum
Discharge Current
|
Short
Circuit Current
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
80 lbs.
36 kg.
|
Absorbed H2SO4
SG= 1.300
|
800 Amps
|
4000 Amps
@ 0.1 sec.
|
0.0030 Ohms
|
|
Capacity
|
100 Ah @ 8 hour rate to 1.75 volts per cell @ 77° F (25°
C)
98.1 Ah @ 10 hour rate to 1.80 volts per cell @ 20° C (68° F)
|
|
Operating Temperature Range
|
Discharge; -40° F ( -40° C) to +160° F (71° C)
|
Charge; -10° F (-23° C) to +140° F (60° C)
(with temperature compensation)
|
|
Nominal Operating Temperature Range
|
+74° F (23°C) to +80° F (27° C)
|
|
Float Charging Voltage
|
13.5 to 13.8 VDC/unit Average @ 77° F (25° C)
|
|
Recommended Maximum Charging Current Limit
|
C/5 amperes (21.8 amps @ 100% depth of discharge)
|
|
Maximum AC Ripple (Charger)
|
0.5% RMS or 1.5% P-P of float charge voltage recommended
for best results.
Maximum voltage allowed = 4% P-P
Maximum current allowed = 5.45 amperes RMS (C/20)
|
|
Self Discharge
|
Dynasty Telecom batteries may be stored for up to 6 months
at 77°F (25° C) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.
|
|
Accessories
|
Inter unit connectors, racks and cabinet systems available.
|
|
Terminal
|
Threaded copper alloy insert terminal to accept 1/4-20
UNC bolt.
|
|
Terminal Hardware Initial Torque
|
110 in.-lbs. (12.4 N-m)
|

| Note: |
Buss connection
designed for 0.375" (1.0 cm) battery spacing. Batteries to be mounted
with 0.3" (0.75 cm) spacing minimum and free air ventilation. Refer
to battery installation and operating instructions for additional
information. Specifications subject to change without notification. |

|
Telecom
Battery Links:
Dynasty
Long Duration Series Telecom Batteries:
Dynasty
Telecom
SAFT Telecom





We also offer our customers, depending
on their needs, different kinds of battery junk removal programs utilizing
EPA approved disposal centers and/or smelters.
|