Valve regulated Battery Designed for Uninterruptable Power Supply (UPS), Emergency Lighting, Communication, General Purpose and Other Float Service Applications.

MPS12-88
Valve Regulated Lead Acid Battery
for standby power
applications
12V 88 AH @ 20 hr rate,
12V 285 watts/cell @ 15 min. rate

FEATURES

  • Robust plate for extended life.
  • Flame-arresting one-way pressure-relief vent for safety and long life.
  • Durable polypropylene container and cover.
  • Thermally welded case-to-cover bond to eliminate leakage.
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.
  • UL-recognized component.
  • Multicell design for economy of installation and maintenance.
  • Can be used in any orientation. Upright, side, or end mounting recommended.
  • Not restricted for air transport – Complies with IATA/ICAO Special Provision A67.
  • Not restricted for surface transport – classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.
  • Not restricted for water transport – classified as non-hazardous material per IMDG Amendment 27.
  • Computer designed lead, low calcium alloy grid for minimal gassing and ease of recycling.

*All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C & D Representative for complete dimensional information.

MPS 12-88 - Specifications
Cells
Per Unit
Voltage
Per Unit
Weight
Electrolyte
Maximum
Discharge Current
Short Circuit Current
Ohms Imped.
60 Hz
6
12.84
64 lbs.
30 kg.
Absorbed H2SO4
SG = 1.300
800 Amps
3300 Amps
@ 0.1 sec.
0.0040 Ohms
Capacity

285 watts per cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C).
88.0 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C)
78.2 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F)

Operating Temperature Range Discharge; -40°F (-40°C) to +160°F (71°C)

Charge; -10°F (-23°C) to +140°F (60°C) (with temperature compensation)

Recommended Operating Temperature Range
+74°F (23°C) to +80°F (27°C)
Float Charging Voltage
13.5 to 13.8 VDC/unit Average @ 77°F (25°C)
Recommended Maximum Charging Current Limit
C/5 amperes (17.6 amperes @ 100% depth of discharge) @ 20 hour rate
Equalization and Cycle Service Charging Service

14.4 to 14.8 VDC/unit Average at 77°F (25°C).

Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Maximum AC ripple voltage allowed = (4% P-P)
Maximum AC ripple current allowed = 4.4 amperes RMS (C/20)

Self Discharge

Dynasty MPS batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required. For higher temperatures the time interval will be shorter.
Accessories
Inter unit connectors, racks and cabinet systems are available.
Terminal
"L" terminal with 0.28" clearance hole to accept 0.25" (6mm) bolt.
Terminal Hardware Initial Torque
65 in.-lbs. (7.35 N-m).
Terminal Hardware Annual Retorque 52 in.-lbs. (5.88 N-m).

 

Hawker
Multi Purpose:



 

 




battery Recycling

We also offer our customers, depending on their needs, different kinds of battery junk removal programs utilizing EPA approved disposal centers and/or smelters.

Service:

We offer our customers just-in-time delivery and inventory.
Overnight delivery within the 48 contiguous states, on most part numbers, is available.

230 West Parkway US · Pompton Plains, NJ 07444
Phone: 973-835-3334. Fax: 973-835-2332

copyright© 1998-2003 Electro Battery Co. Inc.
website updated November 3, 2003 by: Virtual Image