Installation and maintenance programs
are available with custom cabling, racking or cabinets along with chargers,
inverters and power boards.
Electro
Battery is the complete source
for all your battery needs!
230 West Parkway US · Pompton Plains,
NJ 07444
Phone: 973-835-3334. Fax: 973-835-2332
email address: info@electrobattery.com
|


|
Valve Regulated Battery Designed for Uninterruptable
Power Supply (UPS), Emergency Lighting,Communication,General Purpose
and Other Float Service Applications.
|
MPS12-100
Valve Regulated Lead Acid Battery
for standby power applications
12V 100 AH @ 20 hr rate,
12V 330 watts/cell @ 15 min rate
FEATURES
- Robust plate for
extended life.
- Flame-arresting one-way pressure-relief vent for safety and
long life.
- Durable polypropylene
container and cover.
- Thermally welded
case-to-cover bond to eliminate leakage.
- Absorbent Glass Mat
(AGM) technology for efficient gas recombination of up to 99% and freedom
from electrolyte maintenance.
- UL-recognized component.
- Multicell design
for economy of installation and maintenance.
- Can be used in any
orientation. Upright, side, or end mounting recommended.
- Not restricted for
air transport – Complies with IATA/ICAO Special Provision A67.
- Not restricted for
surface transport – classified as non-hazardous material as related
to DOT-CFR Title 49 parts 171-189.
- Not restricted for
water transport – classified as non-hazardous material per IMDG Amendment
27.
- Computer designed
lead, low calcium alloy grid for minimal gassing and ease of recycling.

|
*All dimensions in inches and (millimeters). All dimensions
are for reference only. Contact a C&D Representative for
complete dimensional information.
|
|
MPS12-100 - Specifications
|
|
Cells
Per Unit
|
Voltage
Per Unit
|
Weight
|
Electrolyte
|
Maximum
Discharge Current
|
Short Circuit Current
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
72.0 lbs.
32.5 kg.
|
Absorbed H2SO4
SG = 1.300
|
800 Amps
|
3600 Amps
@ 0.1 sec.
|
0.0035 Ohms
|
Capacity
|
330 watts per
cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C).
100.0 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C).
86.2 Ah @ 10 hr. rate to 1.80 volts per cell @ 20° C (68°F).
|
| Operating Temperature Range |
Discharge; -40°F (-40°C) to +160°F (71°C).
|
Charge; -10°F (-23°C) to +140°F (60°C).
(with temperature compensation)
|
Recommended Operating Temperature Range
|
+74°F (23°C) to +80°F (27°C). |
Float Charging Voltage
|
13.5 to 13.8 VDC/unit Average @ 77°F (25°C). |
Recommended Maximum Charging Current Limit
|
C/5 amperes (20.0 amperes @ 100% depth of discharge)
@ 20 hour rate. |
| Equalization and
Cycle Service Charging Voltage |
14.4 to 14.8 VDC/unit Average at 77°F (25° C). |
| Maximum AC Ripple (Charger) |
0.5% RMS or 1.5%
P-P of float charge voltage recommended for best results.
Maximum AC ripple voltage allowed = (4% P-P).
Maximum AC ripple current allowed = 5.0 amperes rms (C/20).
|
|
Self Discharge
|
Dynasty MPS batteries may be stored for up to 6 months
at 77°F (25°C) and then a freshening charge is required. For higher
temperatures the time interval will be shorter. |
Accessories
|
Inter unit connectors, racks and cabinet systems are
available. |
Terminal
|
"L" terminal with 0.28" clearance hole to accept 0.25"
(6mm) bolt. |
| Terminal Hardware Initial Torque |
65 in.-lbs. (7.35 N-m). |
| Terminal Hardware Annual Retorque |
52 in.-lbs. (5.88 N-m). |

|
Hawker
Multi Purpose:





We also offer our customers, depending
on their needs, different kinds of battery junk removal programs utilizing
EPA approved disposal centers and/or smelters.
|